Model:FC0501U1102
INTRODUCTION:
FC0501U110 automatic burner controls units provide safeguard protection for industrial and commercial gas, oil, or combination burners.
The typical application, of the controller, is industrial heating process, such as iron-steel, glass, ceramics, oil and gas field, and chemical industrial.
– Safety test start, flame monitor and flame safe guard.
– Flame signal switch output.
– 4 LEDs on the front of the device, indicated: power (red),valve(yellow),flame(yellow) and
alarm (red).
– A non-inflammable, plug-in type plastic case.
– Two stages combustion control.
– The switch, in front of controller, is to start/stop the combustion process. It is also a reset of
alarm.
– Different types can be used with UV, ionization or normal light flame sensor.
TECHNICAL data:
Power:220Vac (± 10%),50/60 Hz;(110Vac is available);
Power Consumption: 5 W;
Ambient Temperature:0 ~ 60 °C;
Environment: <90%, no moisture condensation admissible;
Safety Start Testing Time (T1):10S;
Flame Establish Period (T2):15S;
Flame Failure Response Time(FFRT):< 2S;(T1, T2 and FFRT can also be designed by customer's special requirements.)
Protection:IP40;
Max. load per output:
– Flame signal (contact output):<2A;
– Igniter(term. 6):<1A;
– Valves(term. 7,8):<2A;
– Alarm(term.9):<1A;
– Total load:< 5A;
Model No. and flame sensors:
FC0501U220:(220Vac,50/60Hz)
– GreenIsland FUVS series UV flame detectors
– Honeywell C7027A or C7035A
FC0501U110:(110Vac,50/60Hz)
– Same as FC0501U220
FC0501R220:(220Vac,50/60Hz)
–Ionization probe
–Honeywell C7012A(220Vac,50Hz).
FC0501R110:(110Vac,50/60Hz)
–Same as FC0501R220
FC0501L220(220Vac,50/60Hz)
–Normal light
FC0501L110:(110Vac,50/60Hz)
–Same as FC0501L220
SIZE:
Burner Controls Wring Connection:
FC0501U220 have exported to Malaysia,Austrilia and Pakistan.
FC0501R220 have exported to Malaysia and Pakistan.