1. T2X Generator
2. Rated power :75KW-250KW
3. Three Phase-Four Wires system
4. 4 poles/ 1500rpm
5. can be paralleled

 

Basic specification and technical index of compound excitationgenerator

 

1). Voltage ,frequency, power factor

three-phase compound excitation AC generator with a neutralpoint for the star connection. The generator is three phase-fourwires system. (line voltage 400V, phase voltage 230V, frequency50Hz, related power factor is cos=0.8(lag) based on user needs, wealso can provide 60Hz and other voltage generator.

 

2). Power, rotating speed, efficiency, voltage adjusting rate atthe steady stage

 

type

related capacity

related speed

efficiency

voltage adjusting rate

minimum HP of dragging machine

KVA

KW

 ( RPM )

 %

uncontrol

control

T2X-5

6.25

5

1500

79.5

±5

±1

8.43

T2X-7.5

9.38

7.5

1500

81

±5

±1

12.5

T2X-10

12.5

10

1500

82.5

±5

±1

16.3

T2X-12

15

12

1500

83.5

±5

±1

19

T2X-16

20

16

1500

85

±5

±1

26.1

T2X-20

25

20

1500

86

±5

±1

31.2

T2X-24

30

24

1500

87

±5

±1

37

T2X-30

37.5

30

1500

88

±5

±1

45.7

T2X-40

50

40

1500

89

±5

±1

60.3

T2X-50

67.5

50

1500

89.5

±5

±1

74.9

T2X-64

80

64

1500

90

±5

±1

94.8

T2X-75

93.8

75

1500

90.5

±5

±1

110.7

T2X-90

113

90

1500

91

±5

±1

132.6

T2X-120

150

120

1500

91.5

±5

±1

176

T2X-150

188

150

1500

92

±5

±1

219

T2X-200

250

200

1500

92.3

±5

±1

290

T2X-250

313

250

1500

92.5

±5

±1

36.2

 

NOTE: When the related power is 60Hz, the voltage capacity willbe increased to 1.15-1.2 times compared with 50Hz. The voltage hastwo kinds. ( 460V and 480V ).

 

3). the scope of voltage adjustment

when the compound excitation generator is no load, the scope ofvoltage adjustment is 95%~105% of related voltage.

 

4). Voltage adjusting rate at the transient stage

   If the no-load generator rotates at the 103%related speed, the voltage is related number, the electric currentis suddenly increased to 160% related current, the power factordoesn’t exceed 0.4(lag). When 3 phases symmetrical loades reach tobe steady, and then you offload the current suddenly. During thewhole course of sudden load and sudden unload, the generatorvoltage varies at 85%~~120% related voltage. The needing time (i.e. voltage reaction time ) is not more than 1.5 s if the voltagerecovers to be 97%~103% related voltage when sudden load or suddenunload.