We also manufacture:
Stamford: SX460 SX440 AS440 AS480 MX341 MX321 WA440-T
Leroy somer: R230 R250 R448 R449 R450 R438
General: GAVR-8A GAVR-12A GAVR-15A
Basler: EA04C EA05A EA08A EA15A EA350
Marelli: M40FA640A M16FA655A
Marathon: SE350
Charger: ZH-CH28 5A ZH-CH28 10A
1. VR6
VR6 controls the DC exciter field power of conventional, 50 or 60 Hz brushless genera tors. The regulator(VR6) includes frequency compensation with selectable slope, inverse time over-excitation shutdown, solid-state build-up circuitry, single-phase or three-phase voltage sensing, single-phase or three-phase shunt, or permanent magnet power input, and parallel droop compensation, and an accessory input. The accessory input provides compatibility with accessories such as a var/power factor controller.
2. VR6 Technical specification:
Input:
Voltage, rated 120 V 240 V
Voltage, limits 90-140 V 180-280 V
Frequency 50-240 Hz 50-240 Hz
Burden (at rated V) 1440 VA 2400 VA
Output:
Voltage, continuous 65 Vdc 125 Vdc
Voltage, forcing 10 sec. 100 Vdc 200 Vdc
Current, continuous 12 ADC 10 ADC
Current, forcing 10 sec. 25 ADC 20 ADC
Min. Feld resistance 4 Ohms 10 Ohms
Sensing: 100 to 120 V +/-10% with standard 10K Ohm control, 1 phase or 3 phase, 50/60 or 400 Hz;
Paralleling: 1 A or 5 A for 6% droop maximum; 10 VA maximum burden;
Regulation accuracy: +/- 0.5% maximum;
Under frequency protection breakpoints: Adjustable 45 to 65 Hz;
Regulator response: Less than 4 milliseconds;
Thermal stability: Less than 0.5% per 40° Ambi-ent temperature change;
Power dissipation: Less than 50 W at maximum continuous rating.
12V 24V Generator Charger ZH-CH28 5A:
1. Generator charger introduction
Intelligent Charger is specially designed for starting or working of storage battery (especially suited for full-sealed solid wide-temperature storage battery) in diesel engine. It is a intelligent mode of switch structure. It features in constant pressure, constant current, tricking current, resistance of short circuit, and fully automated function.
2. Generator charger specification
Power Input
Voltage 160~250 VAC
Frequency 20~100Hz
DC Output
Voltage 13.8 VDC, Current 5A--when battery group=12V
Voltage 27.6 VDC, Current 3A--when battery group=24V
Charge Mode
Float charge
DC Voltage Regulation
< ± 1%
Efficiency
> 80% @ Full load
Contact Capacity
0.5A @ 120 VAC
Protection
Reverse polarity, over-voltage, short circuit, current limiting
Environment
Operating Temperature: 0~40 ° C
Storage Temperature: -20~60 ° C
Relative Humidity: Maximum 90%
Vibration: 1.5G @ 5~30 Hz / 5.0G @ 30~500 Hz
Dimensions
180(L) x 160(W) x 60 (H) mm
Weight
0.6 Kg ± 2%
3. Main advantages:
-Short Circuit & Reverse Polarity Protection
-Automatic Charging Under All Conditions
-Automatis identify charging voltage of battery group and putout 12V/24V.
-Compact Size & High Efficiency
-Low Battery Voltage Monitor with Dry Contacts Opening or Closing Under Fault
-Charging Current LED Indicators
-No Current Drain When Input Power Is Off