Protection and control of circuit against overload and short circuitin commercial, household and electric equipment installation. The product is suitable for non-frequently making and breaking operation. The product, free of maintenance, can be operated by non-professionals.
*Pole No.: 1, 1P+N, 2, 3, 3P+N, 4
*Rated voltage: AC 230/400V
*Rated current: 1, 2, 3, 4, 6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63 *Tripping curve: B, C, D
*Rated short-circuit capacity(lcn): 10000A
*Rated service short-circuit breaking capacity(lcs): 7500A
*Rated frequency: 50/60Hz
*Rated impulse withstand voltage: 6.2kV
*Energy limiting class: 3
*Electro-mehanical endurance: 8000
*Magnetic releases operate: B curve: Between 3 and 5 In C curve: Between 5 and 10 In D curve: Between 10 and 14 In