Description:
1.Explosion Proof Emergency Lighting2.IP65, WF1, ExdembIICT4
3.Emergency duration:More than 120min
4.Lighting:LED 2x2W
BCJ Series Explosion ProofEmergency Lighting (IIB, IIC, DIP)
- Application
1 Designed for Explosive atmosphere Zone 1, Zone 2 Combustible dust Zone 20, Zone 21, Zone 22 |
2 Designed for Groups IIA, IIB, IIC Temperature classes T1~T4 |
3 Designed for site with explosive atmosphere suchas petroleum exploitation refinery, storage, chemistry, medicine,textile, printing, military and military facilities etc. |
4 Types options: A, B, C, D, E |
5 B type is emergency exclusive type and A, C, D, Etypes are normal and emergency dual propose types. |
- Technical Specification
Lighting Type | Main Parameter |
A type Normal and emergency lighting dual purpose model normal lightinglamp is GLS, SBMV, emergency lighting is LED. | Rated voltage: AC 220V Explosion protection:ExdIIBT4, DIP A20 TA,T4 ExdembIICT4 Matchinglight:BCd200-X Max.length oflamp:195mm Normal lighting:B200, Z125 Emergency lighting: LED 5W Lampholder:E27 Charging time:≤24h Emergency voltage:DC 3.6V Emergency time:≥120min Ingress protection:IP65 Corrosion resistance:WF1 Cable entries specification:G3/4″ Cable, s out diameter:Φ9mm~Φ14mm |
B type Emergency exclusive type, LED bulb, only works under emergencyconditions. |
ICE60079-0, IEC60079-1, IEC60079-7, IEC60079-18,IEC61241-1-1 Rated voltage: AC 220V Explosion protection:ExdIIBT4, DIP A20 TA, T4,ExdembIICT4 Emergency lighting: LED 2×2W Charging time:≤24h Emergency voltage:DC 3.6V Emergency duration:≥120min Ingress protection:IP65 Corrosion resistance:WF1 Cable entries specification:G3/4″ Cable’s outer diameter:Φ9mm~Φ14mm
|
C type Normal and emergency lighting dual purpose type, normal lamp isHPM, HPS, MHI, emergency lamp is LED. |
IEC60079-0, IEC60079-1, IEC60079-7, IEC60079-18,IEC61241-1-1 Rated voltage: AC 220V Explosion protection:ExdIIBT4, DIP A20 TA, T4ExdembIICT4 Matchinglightingd:BCd200-X CCd93(I) CCd93(II) : Max. length of lamp:195mm 185mm 255mm Normal lighting:G80, G125, N70, N100, N110, L70,L100, L150 Emergency lighting: LED 5W Lampholder:E27 Charging time:≤24h Emergency voltage: DC 3.6V Emergency duration:≥120min Ingress protection:IP65 Corrosion resistance: WF1 Cable entries specification:G3/4″
|
D type Normal and emergency lighting dual purpose type, normal andemergency lamps are MHI, electronic ballast, suitable for placeswith high request for continued lighting. |
IEC60079-0, IEC60079-1, IEC60079-7, IEC60079-18,IEC61241-1-1 Rated voltage: AC 220V Explosion protection:ExdIIBT4, DIP A20 TA,T4 ExdembIICT4 Matchinglamp:BCd200-X Max. length oflamp:195mm Normal lighting lamp:L70 Emergency lighting lamp: L70 Lampholder:E27 Charging time:≤24h Emergency voltage:DC 12V emergency duration time:≥45min Ingress protection:IP65 Corrosion resistance:WF1 Cable entries specification:G3/4″
|
E type Normal and emergency lighting double purpose type, using samelamp for normal and emergency lighting, suitable for lamps notrequired ballast. Max power is 70W. |
Rated voltage: AC 220V Matching lightings:BCd200/BCd200-D/BCd250 CCd93(I)/ CCd93(II) Max. length oflamp:190mm/216mm/340mm 185mm/255mm Normal lighting:B60, J27, J30, J42, J55, J68 Emergency lighting:B60, J27, J30, J42, J55, J68 Lampholder:E27 Charging time:≤24h Emergency voltage:DC 6/9.6/12 V Emergency duration:≥45min Ingress protection:IP65 Corrosion resistance:WF1 Cable entries specification :G3/4″
|
- Features
1 Enclosure is die casted of aluminum alloywith high voltage electrostatic powder coated surface after shotblasted.
2 Built-in maintain free battery, charging undernormal conditions, emergency lighting automatically shafted inmatter or power failure status.